Power Quality Analyzer
Wiring connections 1P2W,1P3W, 3P3W, 3P4W
Measurements and parameters
Voltage, Current, Frequency, Active power, Reactive power,Apparent power,Active energy, Reactive energy, Apparent energy, Power factor(cos Î),
Neutral current, Demand, Harmonics, Quality(Swell/Dip/Interruption, Transients/Over voltage, Inrush current, Unbalancerate), Capacitance calculation for PF correction unit, Flicker
Voltage (RMS)
Range 600.0 / 1000V
Accuracy 600.0VRange : (sine wave 40 - 70Hz)
10% - 150% against 100V or more of nominal V : NominalV±0.5%
Out of above range : ±0.2%rdg±0.2%f.s.
1000V Range : ±0.2%rdg±0.2%f.s.(sine wave 40 - 70Hz)
Allowable input 1 -120% of each range (rms). 200% of each range (peak)
Display range 0.15- 130% of each range
Crest factor 3or less
Sampling speed of Voltage transient 24µs
Current (RMS)
Range 8128/8135 (50A type ) : 5000mA / 50.00A / AUTO
8127 ( 100A type ) : 10.00 / 100.0A / AUTO
8126 ( 200A type ) : 20.00 / 200.0A / AUTO
8125 ( 500A type ) : 50.00 / 500.0A / AUTO
8124/8130 ( 1000A type ) : 100.0 / 1000A / AUTO
8146/8147/8148 ( 10A type ) : 1000mA / 10.00A / AUTO
8133 ( 3000A type ) : 300.0 / 3000A / auto
Accuracy ±0.2%rdg±0.2%f.s.+ accuracy of clamp sensor (sine wave, 40 - 70Hz)
Allowable input 1 -110% of each range (rms). 200% of each range (peak)
Display range 0.15- 130% of each range
Crest factor 3or less
Active power:
Accuracy ±0.3%rdg±0.2%f.s.+ accuracy of clamp sensor
(power factor 1, sine wave, 40 - 70Hz)
Influence of power factor ±1.0%rdg(reading at power factor 0.5 against power factor 1)
Frequency meter range 40- 70Hz
Power supply (AC Line) AC100- 240V / 50 - 60Hz / 7VA max
Power supply (DC battery) Alcalinesize AA battery LR6 or Ni-MH (HR-15-51) 6
Battery life approx. 3h (LR6, Backlight OFF)
Internal memory FLASHmemory (4MB)
PC card interface SDcard (2GB)
PC communication interface USBVer2.0, Bluetooth Ver2.1 + EDR Class2
Display 320 240(RGB) Pixel, 3.5inch color TFT display
Display update period 1sec